5 Options with requirements
The following options with requirements as defined in EN 54-2/A1 are available.
The table below explains how to realize these options in the panel.
The relevant sections according to EN 54-2/A1 are specified in the left column of
the table.
EN 54-2
Options with requirements
Function in FC360 series
Installation
Configuration
1
/Operation
Chapter
7.8
Output C to fire alarm devices
according to EN 54-1
Monitored output
Sounder lines
C-NET devices
Sounder control
6
7
8
7.9.1
Output E to fire alarm routing
equipment
according to EN 54-1
Monitored output
card (4M)
RT fire
6.11.4
7.9.2
Alarm confirmation input from fire
alarm routing equipment
Input
RT device confirmation
signal; LED fire brigade
activated via input
6.8
7.10.1
Outputs G to fire protection equipment
according to EN 54-1
Monitored output
card (4M)
Fire output
6.11.4
7.11
Delays to outputs
-
Alarm Verification Concept
Delayed Alarm Reset
'Manned'/ 'Unmanned'
15,
16
7.12.1
Dependencies on more than one
alarm signal, type A dependency
-
Type A inhibit time
30…60 sec.
Reset of the first alarm after
90 sec.
-
7.13
Alarm counter
-
Alarm counter
-
8.3
Fault signals from points
-
RT fault
6.11.4
8.8
Output to fault warning routing
equipment
Relay 2
RT fault
6.5
8.9
Output J to fault warning routing
equipment
according to EN 54-1
Monitored output
card (4M)
RT fault
6.11.4
9.5
Disablement of addressable points
-
Disable
-
10
Test condition
-
Test
-
1
Find more information about configuration in document A6V10450595.