Options with requirements
5 Options with requirements
The following options with requirements as defined in EN 54-2/A1 are available.
The table below explains how to realize these options in the panel.
The relevant sections according to EN 54-2/A1 are specified in the left column of
the table.
EN 54-2
Options with requirements
Output C to fire alarm devices
according to EN 54-1
Monitored output
Sounder lines
C-NET devices
Output E to fire alarm routing
equipment
according to EN 54-1
Monitored output
card (4M)
Alarm confirmation input from fire
alarm routing equipment
↑ RT device confirmation
signal; LED fire brigade
activated via input
Outputs G to fire protection equipment
according to EN 54-1
Monitored output
card (4M)
Alarm Verification Concept
Delayed Alarm Reset
↑ 'Manned'/↑ 'Unmanned'
Dependencies on more than one
alarm signal, type A dependency
Type A inhibit time
30…60 sec.
Reset of the first alarm after
90 sec.
Fault signals from points
Output to fault warning routing
equipment
Output J to fault warning routing
equipment
according to EN 54-1
Monitored output
card (4M)
Disablement of addressable points
Find more information about configuration in document A6V10450595.