8.2 Alarm procedure in manned mode
Display provides fire information. See chapter 'Event views [➙ 66]'.
Immediate activation of panel states 'Any fire'.
In the event of an automatic fire alarm in manned mode, the attendance check
countdown T1 starts if AVC is on.
The Alarm Verification Concept (AVC) for automatic detectors can be deactivated
for special applications. In this case, the alarm procedure follows the description
in chapter 'Alarm procedure in unmanned mode' (i.e. no attendance check T1 and
no investigation time T2).
Press <Acknowledge> to confirm attendance
check.
(Access level 2 password is required.)
→ Buzzer is off.
The investigation time T2 starts.
Optional: Press <Silence/Resound> to
silence/resound all alarm devices.
Read the alarm event information on the LCD and go
to the indicated fire location.
During the investigation time, examine the fire location and decide whether it is a
MAJOR INCIDENT or MINOR INCIDENT.