4
22 | 151
A6V10421795_en--_k
4.4 Technical data
Information on approvals and the relevant EU directives for this device (these
devices) is available in the following document(s); see chapter 'Applicable
documents [➙ 9]':
Document A6V10419665
4.4.1 General data
Detector line
Number of detector lines
Loops or
Stub lines
FC361-xx
Max. 1
Max. 2
FC362-xx
Max. 2
Max. 4
Number of addresses per loop
Max. 126
Max. 126
Number of addresses per stub
Max. 32
Max. 32
Inputs/outputs
Number of sounder circuits
2
Number of relay outputs
3
Number of configurable inputs/outputs
4
Options
RS232/RS485 module
Max. 1
Ext. printer DL3750+
Max. 1
LED indicator (32 zones)
Max. 1
Evacuation module (NL)
Max. 1
Key switch/Key switch (Nordic)
Max. 1
Output card (4M)
Max. 1
Alarm counter
Max. 999 alarms
Event memory
Max. 2000 events