4
24 | 151
A6V10421795_en--_k
Batteries
Operating time
Up to 72 h
Battery capacity
2x 12 V, 7 Ah/12 Ah/25 Ah, sealed
lead acid
Voltage
DC 20.5…28.6 V
Charging current
Max. 1.6 A
Load resistance R
imax
Max. 1 Ω
1
Each sounder line has an output current of max. 0.5 A. The total output current
of both sounder lines is max. 0.5 A.
2
Each configurable IO on the mainboard has an output current of max. 0.1 A.
The total output current of configurable IOs and aux. power output is
max. 0.2 A.
3
Each output on the output card (4M) has the capability of max. 1.0 A. The total
output current of output card (4M) is max. 2.0 A.
4.4.3 Mechanical data
FC361-ZZ/FC362-ZZ
FC361-ZA/FC362-ZA
Terminals
0.2…2.5 mm
2
Dimensions (W x H x D)
402 x 372 x 132 mm
402 x 372 x 211 mm
Weight (without batteries)
5.13 kg/5.15 kg
6.32 kg/6.34 kg
Color
- Housing, Cover
~RAL 7035, light gray
4.4.4 Environmental conditions
Operating temperature
-5…+40 °C
Storage temperature
-20…+60 °C
Air humidity (no condensation permitted)
≤95 % rel.
Protection category (IEC 60529)
IP30