EasyManua.ls Logo

Siemens FC361 Series - Function overview; Access levels

Siemens FC361 Series
151 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function overview
Access levels
7
A6V10421795_en--_k
59 | 151
7 Function overview
7.1 Access levels
The panel is protected against unauthorized operation by access levels.
The authorization passwords for access level 2, access level 3 and access
level 3.1 can be changed either directly on panel or with 'FC360 Panel
Configurator'.
Acces
s level
Personnel
Password
(Default)
Function
1
Anybody
No
View pending events.
2
Authorized user
1234 or
key switch
or input
Operate the system, e.g.
Acknowledge, operate and reset
events.
Disable/enable zone, device, alarm
devices, RT alarm, and RT fault.
Perform detection test, lamp test
1
and
voice test
View event log and compensation
value log.
Automatic logout after a period of no
operation.
Access code is not necessary if a key
switch is used.
Access code is not necessary if the
input configured as ‘access level 2’ is
activated.
3
Commissioning
engineer
9999
Configure system.
Automatic logout after a period of no
operation.
3.1
9999
Restart a detector line.
4
66666666
Reset alarm counter.
1
This function is available directly under Main menu for access level 1 if
checkbox 'Lamp test activation possible at access level 1' is checked under
task card 'Other settings' in 'FC360 Panel Configurator'.

Table of Contents