Message input from the power supply: Battery fault
Message input from the power supply: Mains fault
Supply input from the power supply (+)
Supply input from the power supply (+)
Supply input from the power supply (-)
Supply input from the power supply (-)
Panel shuts down and restarts.
S2: Reset key for detection module (for factory use only)
The C-NET detector lines are powered off and the panel
reports a fatal fault of detection module. You can power
on the C-NET detector lines and remove the fatal fault by
'Reset detection module' function. See 'Reset detection
module [➙ 100]'.
NOTICE! Do not use! For factory use only! Otherwise
a fatal error will occur!
Buzzer enabled (default).
Buzzer disabled.
Note: Only disable the buzzer for commissioning
purpose. Otherwise, keep it enabled to comply with
EN 54-2.
S4: Switch for earth fault detection
Earth fault monitoring activated (default).
Earth fault monitoring deactivated.
Note: Only deactivate the earth fault detection for
commissioning purpose. Otherwise, keep it activated to
comply with EN 54-2.