Installation
Accessories
6
A6V10421795_en--_k
51 | 151
The table below can be used for this check, they display the maximum values.
Details must be calculated individually.
Imax
R Line [] @ Umin = 16 V
0.1 A
0…74.3
0.2 A
0…34.1
0.4 A
0…14
0.6 A
0…7.2
0.8 A
0…3.9
1 A
0…1.9
Counteractive measures: Reduction of I Load or R Line