Settings
10.2 Set Actual Value/Set Actual Value on-the-fly/Cancel Set Actual Value
FM 352 electronic cam controller
106 Operating Instructions, 05/2011, A5E01071724-03
Table 10- 1 Shift of the coordinate system by "Set Actual Value" / "Set Actual Value on-the-Fly"
Set actual value SLS
[mm]
REF
[mm]
ACT
[mm]
SLE
[mm]
-400
-200
200
400
6/6 6/(
5() $&7
  
>PP@
  
>PP@
2IIVHW
RIFRRUGLQDWH
V\VWHP
E\PP
6HWDFWXDOYDOXH
WRPP
2OGFRRUGLQDWHV\VWHP
$[LV
:RUNLQJbUDQJH
1HZFRRUGLQDWHV\VWHP
-200
0
400
600
Canceling the setting
The "Cancel set actual value" can be used to reset the coordinate shift caused by "Set actual
value" or "Set actual value on-the-fly".
Once "set actual value on-the-fly" has been triggered, it can no longer be deleted before
execution by a positive edge at input I1. However, it can be overwritten by a new "Set actual
value on-the-fly".
These settings will be reset at the next start of the module.
Parameter used in the channel DB
Address Name Type Start value Comment
35.2 AVALREM_EN BOOL FALSE 1: Cancel actual value setting
Possible causes of error
"Set actual value on-the-fly" and "Retrigger reference point" may not be executed in parallel.
The "set actual value on-the-fly" can be monitored in order to signal an operating error if this
setting causes a software limit switch to exceed the permissible traversing range at a
positive edge at input I1. This operating error is signaled by a diagnostic interrupt, and
written to the diagnostic buffer.