Diagnostics
12
12.1 Possibilities for error evaluation
Overview
With the programming device/PC, you can read out the diagnostic buffer with the
parameter assignment user interface using Test > Error Evaluation.
You will see the error class and error number along with plain text.
You can evaluate errors in your program. The following options are available:
The RETVAL return values in the instance DBs of the integrated FBs as a group
display for errors that occurred during execution of the FBs.
The error bits of the jobs as a group display for errors that occurred while executing a
job.
The error bit DATA_ERR as a group display for an error detected by the FM 352
during a write job.
The error identifier in JOB_ERR, for the cause of an error during communication
between the FB and FM 352.
FB CAM_DIAG for reading out the diagnostic buffer of the FM 352. Here, you can find
out the causes of errors in jobs and asynchronous events (operating errors, diagnostic
errors).
Diagnostic interrupts for fast reaction to events.