7.2 FC CAM_INIT (FC 0)
FM 352 electronic cam controller
42 Operating Instructions, 05/2011, A5E01071724-03
7.2 FC CAM_INIT (FC 0)
Tasks
FC CAM_INIT initializes the following data in the channel DB:
The control signals
The checkback signals
The trigger, done and error bits of the jobs
The function switches and their done and error bits
Job management and the internal buffers for FB CAM_CTRL
Call
The function must be executed after a startup, i.e., after the power supply to the module or
CPU is switched on. You should therefore insert it, for example, in the restart OB (OB100)
and the removal/insertion OB (OB83) or call it in the initialization phase of your user
program. This ensures that your user program does not access obsolete data after a CPU or
module restart.
Call parameters
Name Data type P-type Meaning
DB_NO INT I Number of the channel DB
Return values
This function does not return a return value.