Programming the FM 352
7.1 Basics of Programming an FM 352
FM 352 electronic cam controller
Operating Instructions, 05/2011, A5E01071724-03
41
Enter the module address in the channel DB and, if necessary, also in the diagnostic DB
in the MOD_ADDR parameter.
Proceed as follows to enter the module address:
Recommended procedure:
Assign the module address to the channel DB/diagnostic DB in the user program so
that the assignment of the module address takes place when you call the user
program in OB 100.
Alternative procedure:
You can have the module address entered automatically if you select the module in
HW Config, open the "Properties" dialog with the menu command Edit > Object
Properties, and use the "Mod_Adr" button there to select a channel DB and diagnostic
DB, if necessary. But in this case the values entered in the channel DB/diagnostic DB
(including the module address) are reset to their initial values in the event of a
consistency check (menu command Edit > Check block consistency opens the "Check
block consistency" dialog) followed by a compilation (menu command Program >
Compile All in the "Check block consistency" dialog box).
The values are not changed if there is only a consistency check without compilation.
The menu command Edit > Compile All is only required within the consistency check if
the project was last edited with STEP 7 V5.0 Service Pack 2 or later.
If your PG/PC is connected to a CPU, you can now download the blocks to the CPU.