Data blocks / error lists
C.3 Data and Structure of the Diagnostic DB
FM 352 electronic cam controller
Operating Instructions, 05/2011, A5E01071724-03
189
JOB_ERR
(hex)
JOB_ERR
(dec)
JOB_ERR
(int)
Meaning
80C4 32964 -32572 Communication errors
80C5 32965 -32571 Distributed I/Os not available.
80C6 32966 -32570 Priority class abort (restart or background)
8522 34082 -31454 Channel DB or parameter DB too short. The data cannot be
read from the DB. (write job)
8532 34098 -31438 DB number of the parameter DB too high. (write job)
853A 34106 -31430 Parameter DB does not exist. (write job)
8544 34116 -31420 Error in nth (n > 1) read access to a DB after error occurred.
(write job)
8723 34595 -30941 Channel DB or parameter DB too short. The data cannot be
written to the DB. (read job)
8730 34608 -30928 Parameter DB on the CPU write-protected. The data cannot
be written to the DB (read job).
8732 34610 -30926 DB number of the parameter DB too high. (read job)
873A 34618 -30918 Parameter DB does not exist. (read job)
8745 34629 -30907 Error in nth (n > 1) write access to a DB after error occurred.
(read job)
The errors 80A2 to 80A4 and 80Cx are temporary, i.e. these can be cleared after a waiting time
without user intervention. Messages in the form 7xxx indicate temporary states in communication.