Machine and cam data
9.12 Quantity framework and track data
FM 352 electronic cam controller
Operating Instructions, 05/2011, A5E01071724-03
95
Enable input
Address Name Type Start value Comment
95.0
EN_IN_I3
BOOL
FALSE
Enable input
1 = track signal track 3 AND enable input I3
Bits 95.1 to 95.7 must be 0.
The track signal Q3 is activated when all the following conditions have been met:
• The track is enabled with TRACK_EN.
• The relevant external enable input I3 is set.
• The track result of the track = 1.
Special tracks
Address Name Type Start value Comment
99.0
99.1
99.2
SPEC_TRC0
SPEC_TRC1
SPEC_TRC2
BOOL
BOOL
BOOL
FALSE
FALSE
FALSE
Special tracks
1 = track 0 is counter cam track
1 = track 1 is counter cam track
1 = track 2 is brake cam track
You can assign tracks 0, 1 and 2 as special tracks.
High count value of counter cam track
Address Name Type Start value Comment
100.0
104.0
CNT_LIM0
CNT_LIM1
DINT
DINT
L#2
L#2
High count value of counter cam track
(track 0)
High count value of counter cam track
(track 1)
Range: 2 ... 65535
With this machine data, you define the high count value of the assigned counter cam track.