Digital electronic modules
3.19 2RO NO 24 VDC to 120 VDC/5 A, 24 VDC to 230 VAC/5 A digital electronic module (6ES7132-4HB01-
0AB0)
ET 200S
3-80 Manual, Edition 10/2005, A5E00514527-01
Galvanic isolation
• Between the channels
Yes
• Between the channels and backplane bus
Yes
• Between the channels and supply voltage
Yes
• Between the supply voltage and backplane
bus
Yes
Permissible potential difference
• Between the supply voltage and backplane
bus
75 VDC / 60 VAC
• Between channels and backplane bus
240 VAC
• Between the channels and supply voltage
240 VAC
Insulation tested Yes
• Between the supply voltage and backplane
bus
500 VDC
• Between channels and backplane bus
1500 VAC
• Between the channels and supply voltage
1500 VAC
Current consumption
• From the power supply L+
max. 30 mA
Power dissipation of the module Typically 0.6 W
Status, interrupts, diagnostics
Status display Green LED per channel
Diagnostics function no
Data for selecting an actuator
Output current
• Continuous thermal current
max. 5 A
• Min. load current
8 mA
• min. voltage
17 V
Connecting two outputs in parallel
• For redundant triggering of a load
no
• To increase performance
no
Control of a digital input Yes
Switch rate
• For resistive load
2 Hz
• On inductive load
0.5 Hz
• For lamp load
2 Hz
Limitation (internal) of the voltage induced on
circuit interruption
no
Short-circuit protection of the output
1
no
1
The relay outputs must be fused externally with 6 A.