EasyManua.ls Logo

Siemens Simantic ET 200S - Parameters for 4 DI NAMUR; Table 3-2 Parameters for 4 DI NAMUR

Siemens Simantic ET 200S
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Digital electronic modules
3.1 Parameters for digital electronic modules
ET 200S
3-2 Manual, Edition 10/2005, A5E00514527-01
2DI 24 VDC
High Feature
4DI 24 VDC
High Feature
4DI 24 to 48
VUC High
Feature
2DI/ 4DI 24 VDC
Standard
4DI 24 VDC/SRC
Standard
2DI 120 VAC
Standard
4DI 230 VAC
Standard
Range of values Default
setting
Applicability
Channel 0
Trigger for
hardware
interrupt,
rising edge
3
Channel 1
Channel 2 ---
Trigger for
hardware
interrupt,
rising edge
3
--- ---
disable
Enable
disable
Channel 3
1
The input delay applies to "0" to "1" and to "1" to "0".
2
Short circuit of the sensor supply.
3
Can only be assigned parameters for the IM151-1 High Feature interface module and the IM151-7 CPU
4
If the wire break check is activated, all the unused inputs must be stabilized to prevent them from triggering a module
wire break. To do this, connect a resistor between terminal 24/48 V (3, A4, 7, A8) and the free input. The resistor must
provide at least 0.5 mA of input current (see "Sensor Switching" in the table of technical specifications). This ensures that
sufficient current is flowing to prevent wire break detection.
The sensor must supply at least 0.5 mA when switched off (otherwise wire break will be detected when switched off).
Alternatively, a resistor can be connected parallel to the sensor terminals (the current must be at least 0.5 mA).
3.1.2 Parameters for 4DI NAMUR
This table shows the parameters for 4DI NAMUR:
Table 3-2 Parameters for 4DI NAMUR
4DI NAMUR Range of values Default setting Applicability
Diagnostic interrupt
Enable
disable
disable Module
Encoder type
Channel disabled
NAMUR sensor
Open single contact
Single contact, closed,
with 10 kΩ
NAMUR changeover
contact
Open changeover
contact
Changeover contact,
closed, with 10 kΩ
Channel disabled Channel
Pulse stretching
None
0.5 s
1 s
2 s
None Channel
Diagnostics
Enable
disable Module

Table of Contents

Related product manuals