EasyManua.ls Logo

Siemens Simantic ET 200S - 3.1 Parameters for digital electronic modules

Siemens Simantic ET 200S
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ET 200S
Manual, Edition 10/2005, A5E00514527-01
3-1
Digital electronic modules
3
3.1 3.1 Parameters for digital electronic modules
3.1.1 Parameters for digital input modules
This table shows the parameters for digital input modules:
Table 3-1 Parameters for digital input modules
2DI 24 VDC
High Feature
4DI 24 VDC
High Feature
4DI 24 to 48
VUC High
Feature
2DI/ 4DI 24 VDC
Standard
4DI 24 VDC/SRC
Standard
2DI 120 VAC
Standard
4DI 230 VAC
Standard
Range of values Default
setting
Applicability
Hardware interrupt
3
--- ---
disable
Enable
disable Module
--- Diagnostic
interrupt
---
disable
Enable
disable Module
Input delay
1
--- ---
0.1 ms
0.5 ms
3 ms
15 ms
3 ms Module
Diagnostics:
Short-circuit to M
2
--- ---
disable
Enable
disable Module
--- Diagnostics:
Wire break
4
---
disable
Enable
disable Module
--- Diagnostics:
Blown fuse
---
disable
Enable
disable Module
--- Diagnostics:
No load
voltage
---
disable
Enable
disable Module