EasyManua.ls Logo

Siemens Simantic ET 200S - 2 AI RTD High Feature Analog Electronic Module (6 ES7134-4 NB51-0 AB0)

Siemens Simantic ET 200S
274 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog electronic modules
4.16 2AI RTD High Feature analog electronic module (6ES7134-4NB51-0AB0)
ET 200S
Manual, Edition 10/2005, A5E00514527-01
4-77
Data for selecting a sensor
Input range (rated value)/input resistance
• Resistance-type sensor
150 Ω/min. 2 MΩ
300 Ω/min. 2 MΩ
600 Ω/min. 2 MΩ
• Resistance thermometer
Pt100/min. 2 MΩ
Ni100/min. 2 MΩ
Permitted input voltage (destruction limit) max. 9 V
Connection of the sensors
• For measuring resistance
– Two and three-wire connection
– Four-wire connection
Yes, line resistances are also measured, jumpers at T
R
Yes
Characteristic curve linearization Yes, parameters can be assigned for Pt100, Ni100
Smoothing of the measured values Yes, can be assigned parameters in 4 steps by means of
digital filtering
Step
None
Weak
Medium
Strong
Time constant
1 x cycle time
4 x cycle time
64 x cycle time
128 x cycle time
4.16 4.16 2AI RTD High Feature analog electronic module
(6ES7134-4NB51-0AB0)
Properties
• 2 inputs for resistance thermometers or resistance measurement
• Input ranges
– Resistance thermometers: Pt100; Ni100; Ni120; Pt200; Ni200; Pt500; Ni500; Pt1000;
Ni1000; Cu10; resolution max. 15 bits + sign
– Resistance measurement: 150 Ω; 300 Ω; 600 Ω; 3000 Ω; PTC; resolution max. 15 bits
• Automatic compensation of line resistances in the case of a three-wire connection
• Temperature coefficient can be assigned parameters for resistance-type sensors
• High accuracy
• Isolated from the load voltage
• Linearization of the sensor characteristic curves
• Permitted common-mode voltage 5 VACss
• Recording of reference junction temperature (together with the 2AI TC Standard
electronic module)
• Compatible with the 2AI RTD Standard (6ES7134-4JB50-0AB50)

Table of Contents