Analog electronic modules
4.5 Parameters for analog electronic modules
ET 200S
Manual, Edition 10/2005, A5E00514527-01
4-29
4.5.4 Parameters for analog electronic modules 2AI RTD Standard, 2AI TC Standard
and 2AI TC High Feature
Table 4-33 Parameters for analog input modules RTD, TC
2AI RTD
Standard
2AI TC Standard 2AI TC High
Feature
Range of values Default setting Applicability
Group diagnosis (parameter assignment error,
internal error)
disable
Enable
disable Module
Diagnostics: Overflow/underflow
disable
Enable
disable Module
Diagnostics:
Wire break
2
Diagnostics: Wire break check
1
disable
Enable
disable Channel
Smoothing
None
Weak
Medium
Strong
None Channel
Temperature
unit
Celsius
Fahrenheit
Celsius Module
--- Reference
junction
---
None
RTD
None Channel
--- Reference
junction
None
Yes (i.e. internal)
None Channel
--- Reference
junction number
---
None
1 to 8
(in the case of the IM151-1
STANDARD and
IM151-1 FO STANDARD)
1
(in the case of the IM151-1
BASIC, IM151-1 COMPACT,
IM151-1 HIGH FEATURE)
None Module
Type/range of
measurement
---
De-activated
150 ohm
300 ohm
600 ohm
Pt100 Climatic
Ni100 Climatic Range
Pt100 Standard
Ni100 Standard
Pt100
Standard
Channel
--- Type/range of
measurement
---
De-activated
Voltage ± 80 mV
TC-EL type T (Cu-CuNi)
TC-EL type K (NiCr-Ni)
TC-EL type B (PtRh-PtRh)
TC-EL type N (NiCrSi-NiSi)
TC-EL type E (NiCr-CuNi)
TC-EL type R (PtRh-Pt)
TC-EL type S (PtRh-Pt)
TC-EL type J (Fe-Cu-Ni)
TC-EL type L (Fe-Cu-Ni)
TC-EL type K
(NiCr-Ni)
Channel