EasyManua.ls Logo

Siemens Simantic ET 200S - Table 4-20 SIMATIC S7 Format: Measuring Range Type N in °C and °F

Siemens Simantic ET 200S
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog electronic modules
4.2 Analog value representation
ET 200S
4-12 Manual, Edition 10/2005, A5E00514527-01
Measuring range for thermocouple type N
Table 4-20 SIMATIC S7 format: Measuring range Type N in °C and °F
Units Units
Type N in °C
Decimal Hexadecima
l
Type N in °F
Decimal Hexadeci
mal
Range
> 1550.0 32767 7FFF
H
> 2822.0 32767 7FFF
H
Overflow
1550.0
:
1300.1
15500
:
13001
3C8C
H
:
32C9
H
2822.0
:
2372.1
28220
:
23721
6E3C
H
:
5CA9
H
Overshoot range
1300.0
:
-270.0
13000
:
-2700
32C8
H
:
F574
H
2372.0
:
-454.0
23720
:
-4540
5CA8
H
:
EE44
H
Rated range
< -270.0 -32768 8000
H
-32768 8000
H
<EE44
H
Underflow
Measuring range for thermocouple types R, S
Table 4-21 SIMATIC S7 format: Measuring range Type R, S in °C and °F
Units Units
Type R, S in °C
Decimal Hexadecima
l
Type R, S in °F
Decimal Hexadeci
mal
Range
> 2019.0 32767 7FFF
H
> 3276.6 32767 7FFF
H
Overflow
2019.0
:
1769.1
20190
:
17691
4EDE
H
:
451B
H
3276.6
:
3216.3
32766
:
32163
7FFE
H
:
7DA3
H
Overshoot range
1769.0
:
-50.0
17690
:
-500
451A
H
:
FE0C
H
3216.2
:
-58.0
32162
:
-580
7DA2
H
:
FDBC
H
Rated range
-50.1
:
-170.0
-510
:
-1700
FE0B
H
:
F95C
H
-58.1
:
-274.0
-581
:
-2740
FDBB
H
:
F54C
H
Undershoot
range
< -170.0 -32768 8000
H
< -274.0 -32768 8000
H
Underflow

Table of Contents

Related product manuals