EasyManua.ls Logo

Siemens Simantic ET 200S - Table 4-17 SIMATIC S7 Format: Measuring Range Type J in °C and °F

Siemens Simantic ET 200S
274 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog electronic modules
4.2 Analog value representation
ET 200S
Manual, Edition 10/2005, A5E00514527-01
4-11
Measuring range for thermocouple type J
Table 4-17 SIMATIC S7 format: Measuring range Type J in °C and °F
Units Units
Type J in °C
Decimal Hexadecima
l
Type J in °F
Decimal Hexadeci
mal
Range
> 1450.0 32767 7FFF
H
> 2642.0 32767 7FFF
H
Overflow
1450.0
:
1200.1
14500
:
12010
38A4
H
:
2EEA
H
2642.0
:
2192.1
26420
:
21921
6734
H
:
55A1
H
Overshoot range
1200.0
:
-210.0
12000
:
-2100
2EE0
H
:
F7CC
H
2192.0
:
-346.0
21920
:
-3460
55A0
H
:
F27C
H
Rated range
< -210.0 - 32768 8000
H
< -346.0 - 32768 8000
H
Underflow
Measuring range for thermocouple type K
Table 4-18 SIMATIC S7 format: Measuring range Type K in °C and °F
Units Units
Type K in °C
Decimal Hexadecima
l
Type K in °F
Decimal Hexadeci
mal
Range
> 1622.0 32767 7FFF
H
> 2951.6 32767 7FFF
H
Overflow
1622.0
:
1372.1
16220
:
13721
3F5C
H
:
3599
H
2951.6
:
2501.7
29516
:
25062
734C
H
:
61B9
H
Overshoot range
1372.0
:
-270.0
13720
:
-2700
3589
H
:
F574
H
2501.6
:
-454.0
25061
:
-4540
61B8
H
:
EE44
H
Rated range
< -270.0 - 32768 8000
H
< -454.0 - 32768 8000
H
Underflow
Measuring range for thermocouple type L
Table 4-19 SIMATIC S7 format: Measuring range Type L in °C and °F
Units Units
Type L in °C
Decimal Hexadecima
l
Type L in °F
Decimal Hexadeci
mal
Range
> 1150.0 32767 7FFF
H
> 2102.0 32767 7FFF
H
Overflow
1150.0
:
900.1
11500
:
9001
2CEC
H
:
2329
H
2102.0
:
1652.1
21020
:
16521
521C
H
:
4089
H
Overshoot range
900.0
:
-200.0
9000
:
-2000
2328
H
:
F830
H
1652.0
:
-328.0
16520
:
-3280
4088
H
:
F330
H
Rated range
< -200.0 -32768 8000
H
< -328.0 -32768 8000
H
Underflow

Table of Contents