Analog electronic modules
4.5 Parameters for analog electronic modules
ET 200S
4-26 Manual, Edition 10/2005, A5E00514527-01
4.4.4 Using the shield connection
Rules
To prevent interference we recommend the following with the analog electronic modules:
Use shielded wires to the sensors and actuators.
Lay out the wire shields on the shield connection.
Connect the shield connection with low impedance to the ground bus.
4.5 4.5 Parameters for analog electronic modules
4.5.1 Parameters for analog electronic modules 2AI U Standard, 2AI I 2WIRE Standard,
4AI I 2WIRE Standard, 2AI I 4WIRE Standard
Table 4-30 Parameters for analog input modules U, I Standard
2AI U
Standard
2AI I 2WIRE
Standard
4AI I 2WIRE
Standard
2AI I 4WIRE
Standard
Range of values Default setting Applicability
Group diagnosis (parameter assignment error,
internal error)
disable
Enable
disable Module
Diagnostics: Overflow/underflow
disable
Enable
disable Module
Diagnostics:
wire break
2
Diagnostics:
wire break
Diagnostics:
wire break
1
disable
Enable
disable Channel
Smoothing
None
Weak
Medium
Strong
None Channel
Type/range
of
measuremen
t
--- ---
De-activated
± 5 V
Up to 5 V
± 10 V
± 10 V Channel
--- Type/range of
measurement
---
De-activated
2 WIRE: 4 to 20 mA
2 WIRE: 4 to 20 mA Channel
--- --- Type/range of
measurement
De-activated
4 WIRE: 4 to 20 mA
4 WIRE: ± 20 mA
4 WIRE: 4 to 20 mA Channel
1
Only in the measuring range 4 mA to 20 mA
2
Only in the measuring range 1 V to 5 V