Analog electronic modules
4.5 Parameters for analog electronic modules
ET 200S
4-28 Manual, Edition 10/2005, A5E00514527-01
4.5.3 Parameters for analog electronic modules 2AI U High Speed, 2AI I 2WIRE High
Speed and 2AI I 4WIRE High Speed
Table 4-32 Parameters for analog input modules U, I High Speed
2AI U High Speed 2AI I 2WIRE High
Speed
2AI I 4WIRE High
Speed
Range of values Default setting Applicability
Group diagnosis (parameter assignment error, internal
error)
disable
Enable
disable Module
Diagnostics: Overflow/underflow
disable
Enable
disable Module
--- Diagnostics: Wire
break
Diagnostics: Wire
break
disable
Enable
disable Channel
Smoothing
None
Weak
Medium
Strong
None Channel
Type/range of
measurement
--- ---
De-activated
± 10 V
± 5 V
± 2.5 V
Up to 5 V
± 10 V Channel
--- Type/range of
measurement
---
De-activated
4 to 20 mA
0 to 20 mA
4 to 20 mA Channel
--- --- Type/range of
measurement
De-activated
4 to 20 mA
0 to 20 mA
± 20 mA
4 to 20 mA Channel
Note
If you deactivate a channel of the HIGH SPEED modules, you do not achieve any speed
advantage on account of the measuring procedure used.