Siemens Simantic ET 200S - Table 4-11 SIMATIC S7 Format: Measuring Ranges ni 100, 120, 200, 500, 1000 Climatic in °C and °F

Siemens Simantic ET 200S
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog electronic modules
4.2 Analog value representation
ET 200S
4-8 Manual, Edition 10/2005, A5E00514527-01
Measuring ranges for resistance thermometer Ni x00 Climatic
Table 4-11 SIMATIC S7 format: Measuring ranges Ni 100, 120, 200, 500, 1000 Climatic in °C and °F
Units Units
Ni x00 Climatic in °C
(1 digit = 0.01 °C)
Decimal Hexadecima
l
Ni x00 Climatic in °F
(1 digit = 0.01 °F)
Decimal Hexadeci
mal
Range
> 295.00 32767 7FFF
H
> 325.11 32767 7FFF
H
Overflow
295.00
:
250.01
29500
:
25001
733C
H
:
61A9
H
327.66
:
280.01
32766
:
28001
7FFE
H
:
6D61
H
Overshoot range
250.00
:
-60.00
25000
:
-6000
61A8
H
:
E890
H
280.00
:
-76.00
28000
:
-7600
6D60
H
:
E250
H
Rated range
-60.01
:
-105.00
-6001
:
-10500
E88F
H
:
D6FC
H
-76.01
:
-157.00
-7601
:
-15700
E24F
H
:
C2AC
H
Undershoot
range
< -105.00 -32768 8000
H
< -157.00 -32768 8000
H
Underflow
Measuring ranges for resistance thermometer Cu 10 Standard
Table 4-12 SIMATIC S7 format: Measuring ranges Cu 10 Standard in °C and °F
Units Units
Cu 10 Standard in °C
(1 digit = 0.1 °C)
Decimal Hexadecima
l
Cu 10 Standard in °F
(1 digit = 0.1 °F)
Decimal Hexadeci
mal
Range
> 312.0 32767 7FFF
H
> 593.6 32767 7FFF
H
Overflow
312.0
:
260.1
3120
:
2601
C30
H
:
A29
H
593.6
:
500.1
5936
:
5001
1730
H
:
12D5
H
Overshoot range
260.0
:
-200.0
2600
:
-2000
A28
H
:
F830
H
500.0
:
-328.0
5000
:
-3280
1389
H
:
F330
H
Rated range
-200.1
:
-240.0
-2001
:
-2400
F82F
H
:
F6A0
H
-328.1
:
-400.0
-3281
:
-4000
F32F
H
:
F060
H
Undershoot
range
< -240.0 -32768 8000
H
< -400.0 -32768 8000
H
Underflow