Analog electronic modules
4.5 Parameters for analog electronic modules
ET 200S
4-30 Manual, Edition 10/2005, A5E00514527-01
2AI RTD
Standard
2AI TC Standard 2AI TC High
Feature
Range of values Default setting Applicability
Type/range of
measurement
• De-activated
• Voltage ± 80 mV
• TC-EL type T (Cu-CuNi)
• TC-EL type K (NiCr-Ni)
• TC-EL type B (PtRh-PtRh)
• TC-EL type C (WRe-WRe)
• TC-EL type N (NiCrSi-NiSi)
• TC-EL type E (NiCr-CuNi)
• TC-EL type R (PtRh-Pt)
• TC-EL type S (PtRh-Pt)
• TC-EL type J (Fe-Cu-Ni)
• TC-EL type L (Fe-Cu-Ni)
TC-EL type K
(NiCr-Ni)
Channel
1
Only with thermocouples. A parameter assignment error occurs when the wire break diagnosis is enabled in the voltage
measuring range. The module does not start up.
2
The wire break is only detected with constant-current lines.
See also
Connecting Thermocouples (Page 4-18)
4.5.5 Parameters for 2AI RTD High Feature analog electronic module
Table 4-34 Parameters for 2AI RTD High Feature analog electronic module
Parameters Range of values Default setting Applicability
Group diagnostics
• Disable
• Enable
Disable Module
Diagnostics:
overflow/underflow
• Disable
• Enable
Disable Module
Diagnostics: Wire break
• Disable
1
• Enable
Disable Channel
Smoothing
• None
• Weak
• Medium
• Strong
None Channel
Temperature unit
• Celsius
• Fahrenheit
Celsius Module
Type of measurement
• De-activated
• Four-wire resistor
• Three-wire resistor
• Two-wire resistor
• Four-wire thermal resistor
• Three-wire thermal resistor
• Two-wire thermal resistor
Four-wire thermal
resistor
Channel