Power modules
2.8 Finding the correct power module for an I/O device
ET 200S
2-16 Manual, Edition 10/2005, A5E00514527-01
Terminal module Design
TM-PF30S47-F1
30 (0 30 (0




$8;
3
3
3RWHQWLDOJURXS 3RWHQWLDOJURXS
%DFNSODQHEXV
2.8 2.8 Finding the correct power module for an I/O device
Applicability of power modules
The following table describes which power modules you can use with the different I/O
modules:
Power modules I/O modules
PM-E 24 VDC Can be used with all electronic modules except the 120 VAC Standard, 2DI 230 VAC
Standard, and 2DO 120/230 VAC.
PM-E 24 VDC to 48 VDC Applicable
Can be used with all electronic modules except the 2DI 120 VAC Standard, 2DI 230 VAC
Standard, and 2DO 120 VAC/230 VAC.
For UC electronic modules if the maximum load voltage is 24 VDC and AC is not
required
PM-E 24 VDC to
48 VDC/24 VAC to 230 VAC
Can be used with all electronic modules.
PM-E F pm 24 VDC
PROFIsafe
PM-E F pp 24 VDC
PROFIsafe
PM-E F 24 VDC PROFIsafe
For the fail-safe modules.
See the
ET 200S Distributed I/O System Fail-Safe Modules
manual
PM-D For motor starters and frequency converters.
See
ET 200S Motor Starter
manual
ET 200S FC Frequency Converter
operating
instructions
PM-D F For fail-safe applications with motor starter or frequency converter.
See
ET 200S Motor Starter
manual
ET 200S FC Frequency Converter
operating
instructions