EasyManua.ls Logo

Siemens Simantic ET 200S - Page 206

Siemens Simantic ET 200S
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog electronic modules
4.15 2AI RTD Standard analog electronic module (6ES7134-4JB50-0AB0)
ET 200S
4-76 Manual, Edition 10/2005, A5E00514527-01
Insulation tested 500 VDC
Current consumption
From load voltage L+
max. 30 mA
Power dissipation of the module Typically 0.6 W
Status, interrupts, diagnostics
Diagnostics function
Group error
Red "SF" LED
Diagnostic functions readable
Yes
Analog value generation
Measuring principle Integrative
Integration and cycle time/resolution per
channel:
Integration time can be assigned
parameters
Yes
Interference frequency suppression in
Hz
60 50
Integration time in milliseconds
16.7 20
Conversion time in ms
110 130
Cycle time in ms
Number of active channels per module x conversion time
Resolution (including overrange)
Pt100, Ni100/ 15 bits + sign
150 Ω/14 bits/
300 Ω, 600 Ω/15 bits
Suppression of interference, limits of error
Interference voltage suppression for
f = n x (f1 ± 1 %), (f1 = interference
frequency)
Common-mode interference (U
SS
)
Series-mode interference
(peak interference value < rated value
of input range)
min. 90 dB
min. 70 dB
Crosstalk between the inputs min. -50 dB
Operational limit (in the entire temperature
range, with reference to the input range)
± 0.6 %
Basic error limit (operational limit at 25° C
with reference to input range)
± 0.4 %
Temperature error (with reference to the
input range)
± 0.005 %/K
Linearity error (with reference to the input
range)
± 0.01 %
Repeatability (in steady state at 25° C with
reference to input range)
± 0.05 %

Table of Contents