Analog electronic modules
4.7 2AI U High Feature analog electronic module (6ES7134-4FB00-0AB0)
ET 200S
4-44 Manual, Edition 10/2005, A5E00514527-01
• Resolution (including overrange)
± 10 V/15 bits + sign
± 5 V/15 bits + sign
1 V to 5 V/15 bits
Suppression of interference, limits of error
Interference voltage suppression for
f = n x (f1 ± 0.5 %), (f1 = interference
frequency)
• Common-mode interference (U
SS
)
• Series-mode interference
(peak interference value < rated value of
input range)
• Crosstalk between the inputs
min. 100 dB
min. 90 dB
min. -100 dB
Operational limit
(entire temperature range with reference to
input range; calibration enabled
1
)
± 0.1 %
Operational limit
(entire temperature range with reference to
input range; calibration disabled)
± 0.5%
Basic error limit (operational limit at 25° C with
reference to input range; calibration enabled
1
)
± 0.05%
Temperature error (with reference to input
range; calibration enabled
1
)
± 0.003 %/K
Temperature error (with reference to input
range; calibration disabled)
± 0.015 %/K
Linearity error (with reference to the input
range)
± 0.03%
Repeatability
(in steady state at 25° C with reference to
input range)
± 0.01%
Data for selecting a sensor
Input range (rated value)/input resistance
• Voltage
± 10 V/min. 1 MΩ
± 5 V/min. 1 MΩ
1 V to 5 V/min. 1 MΩ
Permitted input voltage (destruction limit) 35 V continuous, 75 V at max. duration of 1 ms
Smoothing of the measured values Yes, can be assigned parameters in 4 steps by
means of digital filtering
Step
None
Weak
Medium
Strong
Time constant
1 x cycle time
4 x cycle time
32 x cycle time
64 x cycle time
1
Run-time calibration can be enabled during module parameter assignment to adjust for component
drift due to changes in ambient temperature. During the calibration interval, the updating of new data
is delayed by 250 ms. Calibration takes place each time the ambient temperature changes by 5 °C.