Analog electronic modules
4.18 2AI RTD High Feature analog electronic module (6ES7134-4NB01-0AB0)
ET 200S
Manual, Edition 10/2005, A5E00514527-01
4-93
Analog value generation
Measuring principle Integrative
Integration time/conversion time/resolution
per channel:
Integration time can be assigned
parameters
Yes
Interference frequency suppression in
Hz
60 50
Integration time in milliseconds
16.7 20
Basic conversion time incl. integration
time in ms
66 80
Additional conversion time for wire break
check diagnosis in ms
5 5
Cycle time in ms
Number of active channels per module x conversion
time
Resolution (including overrange)
15 bits plus sign
Suppression of interference, limits of error
Interference voltage suppression for
f = n x (f1 ± 1 %), (f1 = interference
frequency)
Common-mode interference (U
SS
)
Series-mode interference
(peak interference value < rated value of
input range)
min. 90 dB
min. 70 dB
Crosstalk between the inputs min. -50 dB
Operational limit for ±80 mV (over the entire
temperature range with reference to the
input range)
± 0.1 %
Operational limit for thermocouples (over
the entire temperature range with reference
to the input range)
1
± 1.5 K
Operational limit for thermocouple type C (in
the entire temperature range with reference
to the input range)
1
± 7 K
Basic error limit for ±80 mV (operational
limit at 25 °C with reference to the input
range)
± 0.05 %
Basic error limit for thermocouples
(operational limit at 25 °C with reference to
input range)
1
± 1 K
Basic error limit for thermocouples of type C
(operational limit at 25 °C with reference to
the input range)
1
± 5 K
Temperature error (with reference to the
input range)
± 0.005 %/K
Linearity error (with reference to the input
range)
± 0.01 %