Analog electronic modules
4.19 2AO U Standard analog electronic module (6ES7135-4FB01-0AB0)
ET 200S
4-98 Manual, Edition 10/2005, A5E00514527-01
Status, interrupts, diagnostics
Diagnostics function
Group error
Red "SF" LED
Diagnostic functions readable
Yes
Analog value generation
Resolution (including overrange) ± 10 V/13 bits + sign
1 to 5 V/12 bits
Cycle time max. 1.5 ms
Settling time
For resistive load
0.1 ms
For capacitive load
0.5 ms
For inductive load
0.5 ms
Substitute value can be assigned parameters Yes
Suppression of interference, limits of error
Crosstalk between the outputs min. -40 dB
Operational limit (in the entire temperature
range, with reference to the output range)
± 0.4 %
Basic error limit (operational limit at 25 °C with
reference to output range)
± 0.2 %
Temperature error (with reference to the
output range)
± 0.01 %/K
Linearity error (with reference to the output
range)
± 0.02 %
Repeatability
(in steady state at 25 °C with reference to
output range)
± 0.05 %
Output ripple (with reference to output range,
bandwidth 0 to 50 kHz)
± 0.02 %
Data for selecting an actuator
Output range (rated value) ± 10 V
1 V to 5 V
Load resistance min. 1.0 kΩ
For capacitive load
max. 1 µF
Short-circuit protection
Yes
Short-circuit voltage
Approx. 25 mA
Destruction limit against voltages/currents
applied from outside
Voltage at the outputs to M
ANA
15 V continuous; 75 V for max. 1 ms
(sampling ratio 1:20)
Current
max. 50 mA DC
Connection of actuators
Two-wire connection
Possible, without compensation of cable resistance
Four-wire connection
Yes

Table of Contents