Analog electronic modules
4.20 2AO U High Feature analog electronic module (6ES7135-4LB02-0AB0)
ET 200S
Manual, Edition 10/2005, A5E00514527-01
4-101
2AO U High Feature Technical Specifications (6ES7135-4LB02-0AB0)
Dimensions and Weight
Dimensions W × H × D (mm)
(the total dimensions depend on the selected
terminal module)
15 x 81 x 52
Weight Approx. 40 g
Data for specific modules
Supports isochronous operation Yes
Number of outputs 2
Cable length
• Shielded
max. 200 m
Parameter length 7 bytes
Voltages, currents, potentials
Rated load voltage L+ (from the power
module)
24 VDC
• Reverse polarity protection
Yes
Galvanic isolation
• Between the channels and backplane bus
Yes
• Between the channels and load voltage L+
Yes
• Between the channels
no
Permissible potential difference
• Between MANA and the central grounding
point (U
iso
)
75 VDC / 60 VAC
Insulation tested 500 VDC
Current consumption
• From load voltage L+
max. 130 mA
Power dissipation of the module max. 2 W
Status, interrupts, diagnostics
Diagnostics function
• Group error display
Red "SF" LED
• Diagnostic information readable
supported
Substitute values can be applied Yes, parameterizable
Analog value generation
Resolution (including sign) ± 10 V/16 bits
1 V to 5 V/14 bits
Conversion time (per channel) max. 1.0 ms
Settling time
• For resistive load
0.1 ms
• For capacitive load
0.5 ms
• For inductive load
0.5 ms