4 IQ-SENSE (6ES7138-4GA00-0AB0)
5.4 Technical Specifications
ET 200S
5-16 Manual, Edition 10/2005, A5E00514527-01
4 IQ-SENSE Technical Specifications (6ES7138-4GA00-0AB0)
Dimensions and Weight
Dimensions W x H x D (mm) 15 x 81 x 52
Weight Approx. 35 g
Data for specific modules
Supports isochronous operation no
Number of inputs 4
Cable length
• Unshielded
max. 50 m
• Shielded
max. 50 m
Parameter length 16 bytes
Voltages, currents, potentials
Rated supply voltage (from the power module) 24 VDC
• Reverse polarity protection
Yes
Galvanic isolation
• Between the channels
no
• Between the channels and backplane bus
Yes
Permissible potential difference
• Between the different circuits
75 VDC / 60 VAC
Insulation test voltage 500 VDC
Current consumption
• From supply voltage
max. 0.3 A
Power dissipation of the module Typically 0.85 W
Status, interrupts, diagnostics
Status display Green LED per channel
Diagnostics function
• Group error
Red "SF" LED
• Diagnostic information can be displayed
Yes
Data for selecting a sensor
Connectable sensors Photoelectric proximity switches with IQ-Sense
Response Times
Cycle time max. 3.24 ms
Reference
For information on the order numbers for connection cables for the 4 IQ-SENSE electronic
modules see the
section on order numbers
in the
ET 200S Operating Instructions
.

Table of Contents