Power modules
2.4 PM-E 24-48 VDC power module (6ES7138-4CA50-0AA0)
ET 200S
2-8 Manual, Edition 10/2005, A5E00514527-01
PM-E 24 VDC to 48 VDC technical specifications (6ES7138-4CA50-0AA0)
Dimensions and Weight
Dimensions W × H × D (mm)
(the total dimensions depend on the selected
terminal module)
15 × 81 × 52
Weight Approx. 35 g
Voltages, currents, potentials
Rated load voltage 24 VDC to 48 VDC
Reverse polarity protection
Yes
Overvoltage protection
no
Protection with automatic circuit breakers yes, tripping characteristic B, C
Max. current-carrying capacity (up to 60° C) 10 A
Short-circuit protection
no
Galvanic isolation
Between rated load voltage and backplane
bus
Yes
Between the power modules
Yes
Insulation test voltage 500 VDC
Current consumption
From the load voltage L+ (no load)
max. 12 mA
Power dissipation of the module typ. 500 mW
Parameter length 3 bytes
Status, interrupts, diagnostics
Diagnostic function Yes
Group error
Load voltage monitoring
Red "SF" LED
Green "PWR" LED
Diagnostic information readable
Yes
Reference