Digital electronic modules
3.13 Standard digital electronic module 4DO 24 VDC/0.5 A (6ES7132-4BD01-0AA0)
ET 200S
Manual, Edition 10/2005, A5E00514527-01
3-55
Voltages, currents, potentials
Rated load voltage L+ (from the power module) 24 VDC
Reverse polarity protection
Yes
1
Total current of the outputs (per module) 2 A
Galvanic isolation
Between the channels
no
Between the channels and backplane bus
Yes
Permissible potential difference
Between the different circuits
75 VDC / 60 VAC
Insulation tested 500 VDC
Current consumption
From the load voltage L+ (no load)
max. 5 mA per channel
Power dissipation of the module Typically 0.8 W
Status, interrupts, diagnostics
Status display Green LED per channel
Diagnostics function no
Data for selecting an actuator
Output voltage
At signal "1"
min. L+ (-1 V)
Output current
At signal "1"
Rated value
Permitted range
0.5 A
7 mA to 0.6 A
With signal "0" (leakage current)
max. 0.3 mA
Output delay (for resistive load)
at "0" to "1"
max. 100 µs
At "1" to "0"
max. 300 µs
Load resistor range 48 Ω to 3.4 kΩ
Lamp load max. 5 W
Connecting two outputs in parallel
For redundant triggering of a load
Yes (per module)
To increase performance
no
Control of a digital input Yes
Switch rate
For resistive load
100 Hz
On inductive load
2 Hz
For lamp load
10 Hz
Limitation (internal) of the voltage induced on
circuit interruption
Typically L+ (-55 to -60 V)
Reverse-voltage proof Yes, if using the same load voltage as at the
power module
2
Short-circuit protection of the output Yes
3
Threshold on
Typ. 0.7 A to 1.5 A
1
Polarity reversal can lead to the digital outputs being connected through.
2
The module must be supplied with voltage.
3
Per channel