EasyManua.ls Logo

Siemens Simantic ET 200S - Page 99

Siemens Simantic ET 200S
274 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Digital electronic modules
3.13 Standard digital electronic module 4DO 24 VDC/0.5 A (6ES7132-4BD01-0AA0)
ET 200S
Manual, Edition 10/2005, A5E00514527-01
3-55
Voltages, currents, potentials
Rated load voltage L+ (from the power module) 24 VDC
• Reverse polarity protection
Yes
1
Total current of the outputs (per module) 2 A
Galvanic isolation
• Between the channels
no
• Between the channels and backplane bus
Yes
Permissible potential difference
• Between the different circuits
75 VDC / 60 VAC
Insulation tested 500 VDC
Current consumption
• From the load voltage L+ (no load)
max. 5 mA per channel
Power dissipation of the module Typically 0.8 W
Status, interrupts, diagnostics
Status display Green LED per channel
Diagnostics function no
Data for selecting an actuator
Output voltage
• At signal "1"
min. L+ (-1 V)
Output current
• At signal "1"
– Rated value
– Permitted range
0.5 A
7 mA to 0.6 A
• With signal "0" (leakage current)
max. 0.3 mA
Output delay (for resistive load)
• at "0" to "1"
max. 100 µs
• At "1" to "0"
max. 300 µs
Load resistor range 48 Ω to 3.4 kΩ
Lamp load max. 5 W
Connecting two outputs in parallel
• For redundant triggering of a load
Yes (per module)
• To increase performance
no
Control of a digital input Yes
Switch rate
• For resistive load
100 Hz
• On inductive load
2 Hz
• For lamp load
10 Hz
Limitation (internal) of the voltage induced on
circuit interruption
Typically L+ (-55 to -60 V)
Reverse-voltage proof Yes, if using the same load voltage as at the
power module
2
Short-circuit protection of the output Yes
3
• Threshold on
Typ. 0.7 A to 1.5 A
1
Polarity reversal can lead to the digital outputs being connected through.
2
The module must be supplied with voltage.
3
Per channel

Table of Contents