OPC UA communication
9.4 Using the S7-1500 CPU as an OPC UA client
Communication
282 Function Manual, 11/2019, A5E03735815-AH
8. Using drag-and-drop, move the "UA_ReadList" instruction into the program editor.
Select the "Multi-instance" call option.
Click the toolbox symbol (LAD and FBD) or the small green box below the instance name
(STL and SCL) if the editor is not already open.
Select the client interface that you want to use. The example uses the "ProductionLine"
client interface.
Under "Data access > Read/Writelist" select the read list that you want to use (in the
example the "Product" read list).
STEP 7 now automatically interconnects all parameters of the "OPC_UA_ReadList"
instruction.
If you want to write data to an OPC UA server, use the "OPC_UA_Write" instruction and
select the list of tags you want to send to the server under "Data access > Writelist"
("ProductionStatus" write list in the example).
9. If you use different read lists or write lists as program-controlled lists in your user
program, move the "
UA_NodeReleaseHandleList" instruction to the program editor using
drag-and-drop operation.
Select the client interface that you want to use.
Now select a read list or write list that you want to release: Only release read or write lists
that you rarely use, since re-registering is time-consuming.
Then, repeat the steps starting with step 7 with the "UA_NodeGetHandleList" instruction.
10. Using drag-and-drop, move the "UA_Disconnect" instruction into the program editor.
Select the "Multi-instance" call option.
Click the toolbox symbol (LAD and FBD) or the small green box below the instance name
(STL and SCL) if the editor is not already open.
Select the client interface that you want to use. The example uses the "ProductionLine"
client interface.
STEP 7 now automatically interconnects all parameters of the "OPC_UA_Disconnect"
instruction.

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals