Data and command errors Error code
[errorCode]
Add info
[errorAd‐
dInfo]
Description
9510 Service mode not active
9530 Weight is outside the permissible tare weight range
9531 Weight is outside the permissible zero setting range
7055 Parameter error DR06 7055 Additional information indicates an implausible parameter in DR06
Parame‐
ter ID
Parameter ID of the affected parameter in DR06
7056 Parameter error DR07 7056 Additional information indicates an implausible parameter in DR07
Parame‐
ter ID
Parameter ID of the affected parameter in DR07
9650 DQ.0 - assignment not possible
9651 DQ.1 - assignment not possible
9652 DQ.2 - assignment not possible
9653 DQ.3 - assignment not possible
7057 Parameter error DR48 7057 Additional information indicates an implausible parameter in DR48
Parame‐
ter ID
Parameter ID of the affected parameter in DR48
7058 Parameter error in
DR11
7058 Additional information indicates an implausible parameter in DR11
Parame‐
ter ID
Parameter ID of the affected parameter in DR11
9510 Service mode not active
7060 Error in extended pa‐
rameters DR 15 - DR 19
7060 Additional information indicates an implausible parameter in DR 15
- DR 19
Parame‐
ter ID
Parameter ID of the affected parameter in DR 15-19
9530 , because weight is outside the permissible tare weight range
7061 Error set point DR 20
or DR 21
7061 Additional information indicates an implausible parameter in DR20/
DR21
Parame‐
ter ID
Parameter ID of the affected parameter in DR 20/DR 21
7062 Error in dosing system
parameters DR 22/DR 23
7062 Additional information indicates an implausible parameter in DR22/
DR23
Parame‐
ter ID
Parameter ID of the affected parameter in DR 22/DR 23
9071 Parameter relation not plausible
5914 Fine flow, coarse/fine dribbling and set point are incompatible
9191 Fine flow is less than the coarse dribbling value
Interrupts/diagnostic messages
9.4 Operating errors
Technology module TM SIWAREX WP351 HF
136 Operating Instructions, 01/2020, A5E47521010-AA

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals