6.5.16 Weighing range data in SecureDisplay [weighingRangeDataInSecureDisplay]
In legal trade operation, the software version of the HMI device must be recorded so that it can
be checked by an official verification officer.
6.5.17 Automatic zero tracking in dosing cycle [automaticZeroTrackingInCycle]
The parameter defines whether the zero tracking (if activated) is to be active only outside the
automatic dosing cycle (only in weighing step 0) or also inside the dosing cycle.
6.5.18 Maximum Tare weight (% of max.) [maxTareWeight]
The parameter is specified as a percentage of the "Maximum weight" parameter. All tare values
(semi-automatic, automatic, or preset tare) are checked for this limit and rejected if the limit is
exceeded.
6.5.19 Initial zero-setting device limit negative (% of max.)
[initialZeroSettingLimitNegative]
Requirement: The Initial zero-setting parameter is enabled.
Max. permissible negative deviation from the calibration zero point. The setting is made in % in
reference to the maximum weight of the weighing range 1.
With scales requiring official calibration, the sum of the negative and positive limit value may not
exceed 20%.
Example
Maximum weighing range = 100 kg
Maximum negative zeroing limit = 10%
→ Up to -10 kg (10% of 100 kg) can be set to zero by the function on power on.
See also
Initial zero-setting [initialZeroSetting] (Page 63)
6.5.20 Initial zero-setting device limit positive (% of max.) [initialZeroSettingLimitPositive]
Requirement: The Initial zero-setting parameter is enabled.
Max. permissible positive deviation from the calibration zero point if the "Initial zero-setting"
function is used. The setting is made in % in reference to the maximum load of the weighing
range 1.
With scales requiring official calibration, the sum of the negative and positive limit value may not
exceed 20%.
Parameter assignment/addressing
6.5 DR03 Calibration parameters
Technology module TM SIWAREX WP351 HF
Operating Instructions, 01/2020, A5E47521010-AA 65

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C