EasyManuals Logo

Siemens SIMATIC ET 200SP Operating Instructions

Siemens SIMATIC ET 200SP
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
6.2.3 Executing commands
Introduction
Data records (DR) are read or written via specific command codes. There are three command
mailboxes within the interface DB for this purpose.
The command mailboxes are managed and processed according to priority. When all three
command mailboxes are triggered at the same time by the user program, the FB executes them
in the following order:
Command
mailbox
Priority Description
Command1 Highest priority If you run cyclic commands in the "Command1" command
mailbox, this makes it impossible to run commands in the
"Command2" or "Command3" command mailbox.
Command2 Medium priority
Command3 Lowest priority Cyclic commands from the "Command3" command mail‐
box are interrupted to run a command in the "Command2"
or "Command1" command mailbox.
You can find a list of all commands in section: Commands (Page 111).
Requirement
You have called the FB (Page 41).
Procedure
1. Open the interface DB.
2. In one of the command mailboxes "Command1", "Command2" or "Command3", enter a
command code for the parameter "code".
Parameter assignment/addressing
6.2 TIA Portal user program
Technology module TM SIWAREX WP351 HF
44 Operating Instructions, 01/2020, A5E47521010-AA

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C