3.3.4 Five basic rules for securing EMC
Observe these five basic rules to secure EMC.
Rule 1: Large area grounding contact
When installing the devices, make sure that the surfaces of inactive metal parts are properly
bonded to chassis ground (see following sections).
Bond all inactive metal parts to chassis ground, ensuring large area and low-impedance
contact (large cross-sections).
When using screw connections on varnished or anodized metal parts, support contact with
special contact washers or remove the protective insulating finish on the points of contact.
Wherever possible, avoid the use of aluminum parts for ground bonding. Aluminum oxidizes
very easily and is therefore less suitable for ground bonding.
Provide a central connection between chassis ground and the ground/protective conductor
system.
Rule 2: Proper cable routing
Organize your wiring system into cable groups (high-voltage/power supply/signal/
measurement/data cables).
Always route high-voltage and data cables in separate ducts or in separate bundles.
Install the measurement cables as close as possible to grounded surfaces (e.g. supporting
beans, metal rails, steel cabinet walls).
Rule 3: Fixing the cable shielding
Ensure proper fixation of the cable shielding.
Always use shielded data cables. Always connect both ends of the data cable shielding to
ground on a large area.
Keep unshielded cable ends as short as possible.
Always use metal/metalized connector housings only for shielded data cables.
Rule 4: Special EMC measures
All inductors that are to be controlled should be connected with suppressors.
For cabinet or enclosure lighting in the immediate range of your controller, use incandescent
lamps or interference suppressed fluorescent lamps.
Installing
3.3 EMC-compliant installation
Technology module TM SIWAREX WP351 HF
20 Operating Instructions, 01/2020, A5E47521010-AA