6.17.4 Tolerance limit TH1 (weight unit) [toleranceLimitTh1]
This parameter defines the limit of the first tolerance band above the set point. The setting
conforms to the selected tolerance reference (percentage or absolute) and must be less than
or equal to tolerance limit TH2.
6.17.5 Tolerance limit TL1 (weight unit) [toleranceLimitTl1]
This parameter defines the limit of the first tolerance band below the set point. The setting
conforms to the selected tolerance reference (percentage or absolute) and must be less than
or equal to tolerance limit TL2 as a positive value.
6.17.6 Tolerance limit TL2 (weight unit) [toleranceLimitTl2]
This parameter defines the limit of the first tolerance band below the set point. The setting
conforms to the selected tolerance reference (percentage or absolute) and must be greater
than or equal to tolerance limit TL1 as a positive value.
6.17.7 Behavior in case of TH1 error [behaviorTh1Violated]
The parameter defines the module response following a tolerance error of class "Greater than
TO1". The following options are available:
0: Weighing cycle is not stopped and is always completed with "Weighing cycle finished".
1: Weighing cycle is stopped. Check the tolerance again using the "Continue" command (code
1141). The cycle is subsequently always completed with "Dosing completed".
2: Weighing cycle is stopped. Check the tolerance again using the "Continue" command (code
1141). If a tolerance error is still present, the weighing cycle is stopped again. This procedure
is repeated until the tolerance error is eliminated (e.g. by manually removing material).
6.17.8 Behavior in case of TL1 error [behaviorTl1Violated]
The parameter defines the module response following a tolerance error of class "Less than
TU1". The following options are available:
0: Weighing cycle is not stopped and is always completed with "Dosing completed".
1: Weighing cycle is stopped. Check the tolerance again using the "Continue" command (code
1141). The cycle is subsequently always completed with "Dosing completed".
2: Weighing cycle is stopped. Check the tolerance again using the "Continue" command (code
1141). If a tolerance error is still present, the weighing cycle is stopped again. This procedure
is repeated until the tolerance error is eliminated (e.g. by manually adding material).
3: Post-dosing with continuous fine signal. Switch the "Fine signal" on continuously until TU1
is exceeded. The tolerance check is performed again and the weighing cycle is completed with
"Dosing completed" as long as a tolerance error is no longer present.
Parameter assignment/addressing
6.17 DR22 Tolerance parameters
Technology module TM SIWAREX WP351 HF
Operating Instructions, 01/2020, A5E47521010-AA 89

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals