Process interfacing via an automation system (PLC, PC)
9.7 Scanner portal application
SIMATIC MV500
206 Operating Instructions, 03/2021, C79000-G8976-C494-05
multiple read results. The master reader itself is also a slave that searches for 1D/2D codes in
the field of view.
Restrictions of the scanner portal application
The scanner portal application is subject to the following restrictions:
All optical readers must operate in the untriggered image acquisition mode "Auto-trigger".
If several different 1D/2D codes with identical contents are read one after the other, the
content is output only once.
The master reader can only output the synchronized result via the TCP interface.
The formatting options of the result string of the master reader are restricted.
A maximum of five optical readers (4 slaves, 1 master) are supported.
If a slave reader is in an error state, the master reader does not change to an error state.
The master reader does not monitor the number of connected slave readers.
Maximum results of 2048 characters including a formatting instruction required for
synchronization can be synchronized.
9.7.1 Configuration
The WBM configuration for the optical readers if you want to set up a scanner portal with
them is described below. A distinction is made between master device and slave devices for
the configuration.
Configuration of the master device
Make the following settings in the WBM for the master device:
Menu: "Program > Image acquisition > Trigger"
To control the image acquisition, select the mode "Auto-trigger" (without "Initial trigger").
Make sure to enter the value "1" in the "Recognize double read" input box.
The acquisition interval must be sufficiently long for the 1D/2D codes in the image to be
read. The interval must be identical on all slave and master devices.
Menu: "Program > Result > Program format text"
Enter the value "\02[CamId]\03%s\04" in the "Format text" input box.
[CamId] can be selected freely and is used to identify the optical reader that read the
1/2D code in the field of view.
The value "\02\03%s\04" is also allowed if no identification of the optical reader is
desired in the result output.
Menu: "Settings > Communication > Interfaces > TCP"
Enter the IP address of the TCP partner of the master device.
Enter the port number of the TCP partner of the master device.