Passive Components for RS-485 Networks
4-3
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Table 4-1 LAN Cables for PROFIBUS (1)
Technical Specifications
1)
Cable Type
FC Standard
Cable
FC FRNC
Cable
FC Food
Cable
FC Robust
Cable
FC Under-
ground Cable
Order Number 6XV1 830
-0EH10
6XV1 830
-0LH10
6XV1 830
-0GH10
6XV1 830
-0JH10
6XV1 830
-3FH10
Attenuation
at 16 MHz
at 4 MHz
at 38.4 kHz
at 9.6 kHz
< 42 dB/km
< 22 dB/km
< 4 dB/km
<2.5 dB/km
< 42 dB/km
< 22 dB/km
< 4 dB/km
<2.5 dB/km
< 42 dB/km
< 22 dB/km
< 4 dB/km
<2.5 dB/km
< 42 dB/km
< 22 dB/km
< 4 dB/km
<2.5 dB/km
< 42 dB/km
< 22 dB/km
< 4 dB/km
<2.5 dB/km
Characteristic impedance
at 9.6 kHz
at 31.25 kHz
at 38.4 kHz
at 3 to 20 MHz
Rated value
270 ± 27 Ω
-
185 ± 18.5 Ω
150 ± 15 Ω
150 Ω
270 ± 27 Ω
-
185 ± 18.5 Ω
150 ± 15 Ω
150 Ω
270 ± 27 Ω
-
185 ± 18.5 Ω
150 ± 15 Ω
150 Ω
270 ± 27 Ω
-
185 ± 18.5 Ω
150 ± 15 Ω
150 Ω
270 ± 27 Ω
-
185 ± 18.5 Ω
150 ± 15 Ω
150 Ω
d.c. loop resistance ≤ 110 Ω /km ≤ 110 Ω /km ≤ 110 Ω /km ≤ 110 Ω /km ≤ 110 Ω /km
Shield resistance ≤ 9.5 Ω /km ≤ 9.5 Ω /km ≤ 9.5 Ω /km ≤ 9.5 Ω /km ≤ 9.5 Ω /km
Effective capacitance at
1 kHz
approx. 28.5
nF/km
approx. 28.5
nF/km
approx. 28.5
nF/km
approx. 28.5
nF/km
approx. 28.5
nF/km
Operating voltage
(effective)
≤ 100 V ≤ 100 V ≤ 100 V ≤ 100 V ≤ 100 V
Cable type
standard code
02YY(ST)CY
1x2x0.64/2.55-
150 KF 40
FRNC VI
02YSH(ST)CH
1x2x0.64/2.55-
150 VI KF25
FRNC
02YSY(ST)C2
Y
1x2x0.64/2.55-
150 KF40
02YSY(ST)C11
Y
1x2x0.64/2.5-
150 KF40
FRNC VI
02YSY(ST)
CY2Y
1x2x0.64/2.5-
150 KF 40 SW
Sheath
Material
Color
Diameter
PVC
violet
8.0 ± 0.4 mm
FRNC
light violet
8.0 ± 0.4 mm
PE
black
8.0 ± 0.4 mm
PUR
violet
8.0 ± 0.4 mm
PE/PVC
black
10.8 ± 0.5 mm
3)
Permitted ambient conditions
– Operating temperature
– Transport/storage
temperature
– Installation temperature
-40°C + 60°C
-40°C + 60°C
-40°C + 60°C
-25°C + 60°C
-25°C + 60°C
-25°C + 60°C
-40°C + 60°C
-40°C + 60°C
-40°C + 60°C
-40°C + 60°C
-40°C + 60°C
-40°C + 60°C
-40°C + 60°C
-40°C + 60°C
-40°C + 60°C
Bending radii
One-time bending
Repeated bending
≥ 75 mm
≥ 150 mm
≥ 75 mm
≥ 150 mm
≥ 75 mm
≥ 150 mm
≥ 75 mm
≥ 150 mm
≥ 80 mm
≥ 150 mm
Max. tensile load 100 N 100 N 100 N 100 N 100 N
Weight approx. 76 kg/km 67 kg/km 67 kg/km 73 kg/km 117 kg/km
Halogen free no yes no no no
Behavior in fire flame-retardant
according to
VDE 0472
T804
test type C
flame-retardant
according to
VDE 0472
T804
test type C
flammable flame-retardant
according to
VDE 0472
T804
test type B
flammable
Oil resistance Conditionally
resistant to mi-
neral oil and
greases
Conditionally
resistant to mi-
neral oil and
greases
Conditionally
resistant to mi-
neral oil and
greases
good resi-
stance to mine-
ral oil and
greases
Conditionally
resistant to mi-
neral oil and
greases

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET PROFIBUS and is the answer not in the manual?

Siemens SIMATIC NET PROFIBUS Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET PROFIBUS
CategoryNetwork Hardware
LanguageEnglish

Related product manuals