EasyManua.ls Logo

Siemens SIMATIC NET PROFIBUS - B.2.2 Instructions for Installing Fine Protection

Siemens SIMATIC NET PROFIBUS
490 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Lightning and Surge Voltage Protection for LAN Cables Between Buildings
B-6
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
B.2.2 Instructions for Installing Fine Protection
The fine protection should be installed as close as possible to the first bus node
following the coarse protection.
The following are required to install the fine protection:
S The base section type no. 919506,
S The protection module MD/HF type no. 919570,
and
S The shield contact terminals type no. 919508
The fine protection should be connected to the reference ground of the first bus
node (for example grounded DIN rail when installing in a cubicle). When installing
the fine protection outside cubicles (IP 65 area or higher) this must be installed in
S protective casing, type no. 906055
as described in the installation instructions for the coarse protection.
Figure B-3 Fine Protection in the cubicle Close to the First Bus Node

Table of Contents

Related product manuals