PROFIBUS NETWORKS
1-10
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
1.2.4 Transmission Techniques According to EIA Standard RS-485
EIA Standard RS-485
The RS-485 transmission technique corresponds to balanced data transmission as
specified in the EIA Standard RS-485 /4/. This transmission technique is
mandatory in the PROFIBUS standard EN 50170 for data transmission on twisted
pair cables.
The medium is a shielded, twisted pair cable.
The bus cable is terminated at both ends with the characteristic impedance. Such
a terminated bus cable is known as a segment.
The attachment of the node to the bus is via a bus terminal with a tap line or a bus
connector (maximum 32 nodes per segment). The individual segments are
interconnected by repeaters.
The maximum length of a segment depends on the following:
S The transmission rate
S The type of cable being used
Advantages:
S Flexible bus or tree structure with repeaters, bus terminals, and bus connectors
for attaching PROFIBUS nodes
S Purely passive passing on of signals allows nodes to be deactivated without
affecting the network (except for the nodes that supply power to the terminating
resistors)
S Simple installation of the bus cable without specialized experience.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET PROFIBUS and is the answer not in the manual?

Siemens SIMATIC NET PROFIBUS Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET PROFIBUS
CategoryNetwork Hardware
LanguageEnglish

Related product manuals