Active Components for RS-485 Networks
5-17
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Connecting the PROFIBUS Cable
Connect the PROFIBUS LAN cable to the PROFIBUS terminator, as follows:
1. Cut the PROFIBUS cable to the required length.
2. Strip the insulation from the PROFIBUS cable as shown in Figure 5-10.
The braid shield must be folded back on to the cable. Only then can the shield
clamp serve as strain relief and as the shield contact.
ÃŽÃŽÃŽ
ÃŽÃŽÃŽ
ÃŽÃŽÃŽ
8,5 16 10
ÃŽÃŽÃŽ
ÃŽÃŽÃŽ
8,5
16 1016
Braid shield must be folded back!
e.g. standard cable
6XV1 830-0EH10
e.g. underground cable
6XV1 830-3FH10
Figure 5-10 Stripping the Insulation to Connect to the PROFIBUS Terminator
3. Connect the PROFIBUS LAN cable to the PROFIBUS terminator:
Connect the same wires (green/red for the PROFIBUS LAN cable) to the same
terminal A or B (in other words always connect terminal A with a green wire and
terminal B with a red wire or vice versa).
4. Tighten the shield clamps so that the shield makes good contact with the clamp.
Note
When installing the segment, make sure that no terminating resistor is activated
on the bus connectors if the two PROFIBUS terminators are included in the
PROFIBUS segment.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET PROFIBUS and is the answer not in the manual?

Siemens SIMATIC NET PROFIBUS Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET PROFIBUS
CategoryNetwork Hardware
LanguageEnglish

Related product manuals