5 LED Indicators and Troubleshooting
Version 1.0 8/00
5.2 Troubleshooting
2. Define the optical receiving level (see 4.4.6 Defining the receiving level of the optical ports, p. 24 and
8.4 Measuring sockets, p. 35):
Level is in the range Function is not guaranteed.
Check the optical fiber absorption using an optical level measuring device.
too high: replace the optical fiber
in valid range: one of the two OLMs of the disturbed optical fiber segments is defective.
First replace the other OLM of the disturbed optical fiber segments (i.e. the OLM, which
supplies the send signal for the measurement described above). If the fault still persists,
replace the other OLM instead.
Level is in the range Optical system reserves reduced or Normal mode.
As described above, check the optical receiving level of the other OLM in the disturbed optical fiber
segment at the appropriate port.
The levels at both OLMs of the disturbed optical fiber segments are in the range Optical system reserves
reduced or Normal mode": one of the two OLMs in the disturbed optical fiber segments is defective.
First replace one of the OLMs in the disturbed optical fiber segment. If the fault still persists, replace the
other OLM instead.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET PROFIBUS and is the answer not in the manual?

Siemens SIMATIC NET PROFIBUS Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET PROFIBUS
CategoryNetwork Hardware
LanguageEnglish

Related product manuals