Configuring Networks
3-20
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Power Budget for OLM G11-1300, G12-1300 for One Point-to-Point
Link at Wavelength
λ = 1310 nm
Attenuation on the cable
Fiber type
Attenuation
a
FOC
Cable length
L
62.5/125 µm 1.0 dB/km 9 km L* a
FOC
= 9.0 dB
+
Attenuation for connectors
a
Conn
Number
+
1 dB 0 Number *
a
Conn
0 dB
Attenuation caused by splices +
a
Spl
Number
0.2 dB 5 Number * a
Spl
1.0 dB
Attenuation of the transmission path a
Path
= 10.0 dB
Data of the OLM/G11-1300, G12-1300 power that
can be coupled into 62.5/125 µm fibers
P
out,
min
–17 dBm
Receiver sensitivity
Prec
,
min
–29 dBm
Maximum permitted attenuation a
max
= P
out,
min
– P
rec,
min
= 12 dB
Link power margin a
max
– a
Path
= 2 dB
The transmission path can be implemented as planned.
Note
The maximum length of fiber-optic cable that can be supplied in one piece depends on the
cable type but is approximately 3 km per drum. Longer links must therefore be put together
using more than one piece of cable. To connect the sections of cable, coupling elements or
splices must be used reducing the maximum possible cable length due to their attenuation.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET PROFIBUS and is the answer not in the manual?

Siemens SIMATIC NET PROFIBUS Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET PROFIBUS
CategoryNetwork Hardware
LanguageEnglish

Related product manuals