Digital Modules
3-25
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Technical specifications of the SM 321; DI 16 x 24 VDC
Dimensions and Weight
Dimensions W x H x D
(in millimeters)
40 x 125 x 117
Weight Approx. 200 g
Data for Specific Module
Supports clocked
operation
Yes
Parameter changing during the
RUN is possible
Yes
Behavior of the non para-
meterized inputs
gives the last valid
output value before the
parameterization
Number of inputs 16
Length of cable
Unshielded
Shielded
max. 600 m
max. 1000 m
Voltages, Currents, Potentials
Power rated voltage of the
electronics and encoder L+
24 VDC
Reverse polarity protection Yes
Number of inputs that can be triggered simultaneously
Horizontal configuration
Up to 60 C 16
Vertical configuration
Up to 40 C 16
Isolation
Between channels and
backplane bus
Yes
Permitted potential difference
Between the different
circuits
75 VDC / 60 VAC
Insulation tested with 500 VDC
Current consumption
From the backplane bus max. 130 mA
From load voltage L +
(without sensor supply VS)
max. 90 mA
Power dissipation of the module typ. 4 W
Status, Interrupts, Diagnostics
Status display
Inputs Green LED per channel
Sensor power supplies (Vs) Green LED per output
Interrupts
Hardware interrupt
Diagnostic interrupt
Parameters can be
assigned
Parameters can be
assigned
Diagnostic functions Parameters can be
assigned
Group error display Red LED (SF)
Diagnostics information
read-out
Possible
Monitoring of
Wire-break yes, at I < 1 mA
Sensor Power Supply Outputs
Number of outputs 2
Output voltage
With load min. L+ (–2.5 V)
Output current
Rated value
Permitted range
120 mA
0 to 150 mA
Additional (redundant) supply Permitted
Short-circuit protection Yes, electronic
Data for Selecting a Sensor
Input voltage
Rated value
For signal “1”
For signal “0”
24 VDC
13 to 30 V
*30 to + 5 V
Input current
At signal “1” typ. 7 mA
Input characteristic curve According to
IEC 61131, type 2
Connection of Two-Wire
BEROs
Permitted bias current
Possible
max. 2 mA
Resistive circuit of the sensor
for detecting broken wires
10 to 18 kOhm
Time/Frequency
Internal processing time for
status processing (in non
synchronous operation)
Release of process and
diagnosis alarm
max. 40 s
Input delay
Parameters can be
assigned
Rated value
Yes
typ. 0.1/0.5/3/15/20 ms