EasyManua.ls Logo

Siemens Simatic S7-300 - Parameters of the SM 331; AI 8 X 16 Bits

Siemens Simatic S7-300
574 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog Modules
4-90
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
An overview of the parameters that you can set and their default settings are
shown in the table below.
Table 4-54 Parameters of the SM 331; AI 8 x 16 bits
Parameter
Value Range Default
settings
Para-
meter Type
Scope
Parameter
Value Range
Default
settings
Para-
meter Type
Scope
Enable
Hardware interrupt if
the limit value is
exceeded
Hardware interrupt at
end of cycle
Diagnostic interrupt
Yes/no
Yes/no
Yes/no
No
No
No
Dynamic
Dynamic
Dynamic
Module
Hardware interrupt trigger
Upper limit
Lower limit
32511 to –32512
–32512 to 32511
Dynamic
Dynamic
Channel
Channel
Diagnostics
Group diagnostics
Wire-Break Check
Yes/no
Yes/no
No
No
Static Channel
Channel
Measurement
Module mode
Interference
Suppression
8 channels
4 channels
50 Hz
60 Hz
400 Hz
50/60/400 Hz
Yes
No
50/60/400 Hz
Dynamic Module
Channel
group
Smoothing None
Low
Average
High
None Dynamic Channel
group
Measuring Method Measuring
Range:
Dynamic Channel
group
Deactivated
Voltage $ 5 V
1 to 5 V
$ 10 V
$ 10 V
Current (4-wire
transmitter)
0 to 20 mA
4 to 20 mA
$ 20 mA
4 to 20 mA