Analog Modules
4-71
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
M
L+
Backplane
bus
DAC
R
L
Q
I
M
ANA
M
internal
L+
M
Ground bus
CPU
Logic
Figure 4-31 Connecting Loads to a Current Output of a Non-Isolated AO
4.16 Diagnostics of the Analog Modules
Programmable and Non-Programmable Diagnostic Messages
In diagnostics, we make a distinction between programmable and
non-programmable diagnostic messages.
You obtain programmable diagnostic messages only if you have enabled
diagnostics by parameter assignment. You perform parameter assignment in the
“Diagnostics” parameter field in STEP 7 (refer to Section 4.7).
Non-programmable diagnostic messages are always made available by the analog
module irrespective of diagnostics being enabled.
Actions following diagnostic message in STEP 7
Each diagnostic message leads to the following actions:
The diagnostic message is entered in the diagnosis of the analog module and
forwarded to the CPU.
The error LED on the analog module lights.
If you have programmed “Enable Diagnostic Interrupt” with STEP 7, a
diagnostic interrupt is triggered and OB 82 is called (refer to Section 4.17).