EasyManua.ls Logo

Siemens Simatic S7-300 - A-33 Codes for the Measuring Ranges of the Analog Input;Output Modules

Siemens Simatic S7-300
574 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Sets for Signal Modules
A-43
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Measuring methods and measuring ranges
The table below contains all the measuring methods and measuring ranges of the
analog input/output modules and their codes. You must enter these codes in bytes
2 to 5 of data record 1 (refer to Figure A-19).
Table A-33 Codes for the Measuring Ranges of the Analog Input/Output Modules
Measuring Method
Code Measuring Range Code
Deactivated 2#0000 Deactivated 2#0000
Voltage 2#0001 0 to 10 V 2#1000
Resistance, four-conductor connection 2#0100 10 k 2#1001
Thermal resistance + linearization
four-conductor connection
2#1000 Pt 100 climate 2#0000
Output methods and output ranges
The table below contains all the output methods and output ranges of the analog
input/output modules and their codes. You must enter these codes in bytes 6 and 7
of data record 1 (refer to Figure A-19).
Table A-34 Codes for the Output Ranges of the Analog Input/Output Modules
Output type
Code Output Range Code
Deactivated 2#0000 Deactivated 2#0000
Voltage 2#0001 0 to 10 V 2#1000